Skip to content

Experiment 101: the 66 labelled real transfers, event by event

Each row is one labelled real transfer, sorted by start. Substations are Primary substations, labelled P followed by the series number; no NGED generator is involved. Share is the moved MW as a share of the metered receivers' usual load (blank when no receiver is metered). Step is the largest 24-hour step in the stored residual within 2 hours of the start, in noise units (blank when the residual panel holds no readings). The last five columns say whether the detector found the event. Back to the write-up.

Event Month Substations Series type Hours Share MW Step D0 PF14 X LOGIT_SAME RO-NC
E01 2022-03 P09 + P24 MVA only 47.6 0.10 0.4 2.4 - - - - -
E02 2022-03 P13 + P16 MW only 30.0 0.27 2.0 6.0 - - yes - -
E03 2022-04 P09 + P24 MVA only 135.2 0.33 1.2 6.3 - yes yes yes yes
E04 2022-04 P15 + P18 mixed 58.9 0.27 0.5 4.1 - yes - - -
E05 2022-04 P17 MW only 4.2 0.24 0.7 2.4 - - - - -
E06 2022-06 P10 + P14 mixed 7.7 1.3 1.8 - - - - -
E07 2022-08 P17 MW only 92.5 0.35 0.8 2.7 - - - - -
E08 2022-08 P10 + P14 mixed 99.8 0.88 1.2 1.5 - - - - -
E09 2022-10 P03 + P14 + P15 MVA only 2.4 0.88 1.0 1.2 - - - - -
E10 2022-10 P13 + P14 mixed 2.7 2.35 2.6 0.8 - - - - -
E11 2022-11 P17 + P18 MW only 8.3 0.15 0.9 4.2 - - - - -
E12 2022-11 P17 + P18 MW only 79.5 0.28 0.9 4.4 - yes yes yes yes
E13 2022-11 P15 + P17 mixed 32.1 0.20 0.7 5.5 - - - - -
E14 2022-12 P15 + P18 mixed 75.1 0.30 0.6 4.3 - yes yes yes yes
E15 2022-12 P15 + P17 mixed 16.2 0.28 1.1 5.1 - - - - -
E16 2023-02 P08 MW only 50.8 0.14 1.1 0.6 - - - - -
E17 2023-03 P17 + P18 MW only 9.1 0.21 1.3 3.7 - - - - -
E18 2023-03 P13 + P16 MW only 4.5 1.4 0.9 - - - - -
E19 2023-03 P17 + P18 MW only 12.6 0.42 1.4 6.8 - - - - -
E20 2023-04 P17 + P18 MW only 8.7 0.16 0.9 2.2 - - - - -
E21 2023-05 P10 + P24 mixed 24.6 0.21 0.4 3.2 - - - - -
E22 2023-05 P09 + P11 MVA only 31.2 0.18 1.0 5.2 - - yes - yes
E23 2023-06 P03 + P15 MVA only 99.8 0.13 0.8 6.0 - - - - -
E24 2023-07 P03 + P15 MVA only 8.1 0.9 1.2 - - - - -
E25 2023-08 P07 + P24 mixed 747.0 1.31 3.9 6.2 - - yes - yes
E26 2023-08 P18 MW only 107.9 0.8 3.4 - - - - yes
E27 2023-09 P03 + P15 MVA only 5.9 1.0 1.7 - - - - -
E28 2023-11 P09 + P24 MVA only 9.0 0.18 0.7 0.8 - - - - -
E29 2023-11 P10 + P14 mixed 4.5 0.36 0.9 2.1 - - - - -
E30 2023-11 P17 + P26 mixed 383.6 0.28 0.9 4.3 - - - - -
E31 2023-12 P09 + P24 MVA only 31.8 0.17 0.6 4.2 - yes yes yes yes
E32 2024-01 P18 MW only 8.9 1.0 0.7 - - - - -
E33 2024-02 P15 + P17 mixed 5.1 1.1 3.7 - - - - -
E34 2024-02 P17 MW only 118.4 0.9 3.6 - - - - yes
E35 2024-04 P09 + P24 MVA only 54.9 0.17 0.6 4.0 - yes - yes yes
E36 2024-05 P09 + P24 MVA only 7.4 0.26 0.8 2.5 - - - - -
E37 2024-05 P17 MW only 8.4 1.2 3.4 - - - - -
E38 2024-06 P17 + P18 MW only 101.0 0.36 0.8 5.4 yes yes yes yes yes
E39 2024-09 P10 + P24 mixed 415.4 0.33 0.6 3.3 - - - - -
E40 2024-09 P03 + P26 MVA only 54.2 0.37 2.5 9.3 - - yes - yes
E41 2024-10 P14 + P16 mixed 71.5 0.50 0.9 3.5 - - - - -
E42 2024-11 P11 + P25 MVA only 7.9 0.15 1.7 2.6 - - - - -
E43 2025-01 P18 MW only 76.8 0.5 1.7 - - - - -
E44 2025-03 P12 + P13 MW only 52.1 0.7 - - - - -
E45 2025-03 P18 MW only 245.9 0.17 1.1 5.4 - - - - -
E46 2025-03 P14 + P15 MVA only 4.2 0.66 1.0 1.5 - - - - -
E47 2025-04 P09 + P11 MVA only 84.3 0.29 1.0 6.4 - - - - -
E48 2025-05 P12 + P13 MW only 2.7 0.3 - - - - -
E49 2025-07 P12 + P13 MW only 52.4 2.0 - - - - -
E50 2025-07 P12 + P13 MW only 75.4 1.6 - - - - -
E51 2025-07 P03 + P16 mixed 6.0 1.0 1.5 - - - - -
E52 2025-09 P12 + P13 MW only 51.2 2.9 - - - - -
E53 2025-10 P03 + P16 mixed 15.3 0.51 3.3 7.7 - - - - -
E54 2025-10 P12 + P13 MW only 50.5 3.0 - - - - -
E55 2025-10 P13 + P14 mixed 47.9 2.2 1.9 - - - - -
E56 2025-11 P10 + P14 mixed 11.8 1.33 1.7 1.6 - - - - -
E57 2025-12 P12 + P13 MW only 2.8 0.7 - - - - -
E58 2025-12 P17 MW only 580.1 0.23 0.9 3.5 - - - - -
E59 2025-12 P12 + P13 MW only 28.2 1.3 - - - - -
E60 2025-12 P03 + P15 MVA only 3.4 0.16 1.4 4.0 - - - - -
E61 2025-12 P17 + P18 MW only 370.5 0.20 1.5 9.4 yes yes yes yes yes
E62 2026-01 P12 + P13 MW only 4.8 0.4 - - - - -
E63 2026-01 P09 + P11 MVA only 4.5 0.13 0.7 1.3 - - - - -
E64 2026-02 P17 + P18 MW only 5.5 0.66 2.8 3.6 - - - - -
E65 2026-03 P03 + P16 mixed 11.5 0.10 0.8 2.5 - - - - -
E66 2026-03 P15 MVA only 3.9 0.30 0.6 3.2 - - - - -