Experiment 73: can the mix of solar panel orientations and the DC to AC ratio be recovered?

We asked whether two properties of the solar panels behind a substation can be read from the substation's power alone. The first is the share of panels facing east, south, and west. The second is the ratio of DC capacity to AC (inverter) capacity, which sets the level at which output flattens at midday. We tested each fit first on answers we know. We added made-up east-south-west output, and the real output of 6 metered solar farms, to the real power of 8 Primary substations (the substations in Lincolnshire that step power down to the local electricity network and are metered in MW), and checked what the fit recovered. The orientation fit has three non-negative capacities, one per orientation. We scored it by total-variation error, the share of capacity assigned to the wrong orientation (0 is exact and 1 is the worst possible).

With no noise added, the median error over the injected cases was 0.09, against 0.30 for always guessing the usual fleet mix (0.2 east, 0.6 south, 0.2 west). With the real series' noise added the median error rose to 0.20. On the real power, the fitted shares changed by a median 0.24 between consecutive September-to-August years. Even so, a blend of the three shapes predicted 28-day blocks of power that the fit had not seen 1.3% better than assuming every panel faces south.

The DC:AC search tries ratios from 1.00 to 1.60 and keeps the one whose clipped shape fits best. The search found each farm's ratio from the farm's own output, but not once the farm's output was added to a Primary's power, so we dropped the search before touching the real series.

Take-home message: the fitted solar shape, a blend of three shapes, is a better solar shape than all-south panels at every one of the 8 Primaries, but it is a more flexible shape and not a measurement of panel orientation. The shares that make up the blend swap from year to year and miss by about 0.2 on a noisy known answer, so none of them should be published as a finding about a Primary's panels. The DC:AC search did not recover a farm's ratio once the farm was added to a Primary's power, so the solar term keeps the fixed ratio of 1.15. The next test is whether the three-shape blend lowers the error of the forecasts of experiment 64 (PVDIS-5), and not only the error of the fit.

Verdict partly supported, read by the rule written before the run. Orientation passes its pre-registered known answers (median share error 0.088, at most 0.15; upper limit of C1, the fit's error minus the guess's, -0.122, below -0.10) and gains on held-out blocks (upper limit of C3, the change in held-out error against all-south panels, -0.54%, below -0.5%). DC:AC is not identified. Exactly one part is identified with its held-out gain, which is the rule's partly supported. After the code review we added a known-answer test that carries noise, because the pre-registered one cannot fail (see below). The chosen arm fails the added test (median error 0.200, C1 upper limit -0.075), so the shares are not identified, and the verdict describes the blend and not the shares.

Figure 1: clear-day output of the six solar farms against irradiance

Figure 2: east, south, and west shapes through one clear day

Known answers

Without noise, injected east-south-west mixes are recovered far better than a guess. The arm chosen on the tuning units (solar-farm locations A to C) was the pooled fit with no prior. On the scoring units (locations D to F) its median share error is 0.088, against 0.300 for guessing the fleet mix. C1, the arm's error minus the guess's, is -0.181 (98.75% interval -0.228 to -0.122), pooled over the five true mixes. With Primaries as the clusters the interval is -0.248 to -0.084. Per true mix, the guess is exact at the fleet mix itself and the fit is not, and the fit wins at the other four. Of the noise-free scoring units at the fitted tilt, 0.192 hit one of the two bounds (a negative increment set to zero, or a total increment under 0.3 MW).

A known-answer test that adds no noise cannot fail. A least-squares fit is linear, so the fitted capacities with and without an injection differ by the fit of the injection alone, whatever the series' own noise. The first test therefore measures only the sky mismatch between the farm location and the Primary, plus the cases where the non-negative constraint binds. The code review found this. We added a second test (post hoc, after the code review and before its result was seen). It builds a series with no solar of its own: the Primary's fitted solar is added back, the part left after removing the calendar cells and the weather terms is shuffled between days of the same month, and the known output is subtracted. The fit then has to find the injection in the real series' noise, and is scored on its fitted capacities directly.

True mix (east/south/west) Pooled fit, no noise Pooled fit, with noise Guess: fleet mix Guess: all south
all south (0/1/0) 0.102 0.315 0.400 0.000
fleet mix (0.2/0.6/0.2) 0.097 0.226 0.000 0.400
east-heavy (0.5/0.4/0.1) 0.097 0.198 0.300 0.600
west-heavy (0.1/0.4/0.5) 0.100 0.190 0.300 0.600
east and west (0.5/0/0.5) 0.045 0.084 0.600 1.000

With noise, the pooled fit's median error on the scoring units is 0.200 against 0.300 for the guess. The noisy C1 is -0.107 (98.75% interval -0.139 to -0.075), so the upper limit of the noisy C1 does not reach -0.10, and the noisy median error is above 0.15. The free fit on each season-year scores 0.169, the clear-day fit 0.296, and the pooled fit with the smallest prior 0.177. All arms miss by more than 0.15 at the tilt of the fit, so the shares are not identified.

Figure 3: share error by true mix, with and without noise

The robustness arm shows the fragility. Injected shapes at 15° and 40° tilt, with the fit at 25°, gave noisy median errors for the pooled fit of 0.277 and 0.163 over all farm locations.

The DC:AC ratio is found from a farm's own output and lost once the farm is added to a Primary. The knee gate was applied to each farm's median across its farm-years, not to each farm-year as the rule states. That median number of clear-day half-hours at or above the knee at ratio 1.15 is 165 to 188 for five farms and 110.5 for farm D, against the threshold of 100, so the gate passed. Three of the 37 farm-years fall below 100 (the lowest has 84). The search on each farm's output alone has a median absolute error of 0.055 over the 6 farms and beats the constant guess (the median ratio of the other five farms) on 5 of 6. With 10 MW of the farm's output added to a Primary's power, the median error is 0.195 and the search beats the guess on 0 of 6, so DC:AC is not identified. The searched ratio sits at 1.00 to 1.10 for every farm in that case. The Primary's own solar is still in the series, so this case measures a farm plus a fleet, and not only the farm.

Farm True ratio Error, farm alone Error, added to a Primary Error of the guess
A 1.15 0.050 0.150 0.070
B 1.17 0.020 0.170 0.050
C 1.22 0.070 0.220 0.050
D 1.42 0.220 0.320 0.250
E 1.12 0.030 0.120 0.100
F 1.26 0.060 0.260 0.090

Figure 4: searched ratio against true ratio

The ratios of experiment 29 come from the same CAMS irradiance and the same clipping form as the search, so the farm-alone case is the easiest test of the search. With 6 farms the intervals are descriptive, and the decision rests on the number of farms, out of 6, where the fit beats the constant guess.

The real series

The shares of the real series are not stable. The free fit to each Primary-year changes its shares by a median total-variation distance of 0.237 between consecutive September-to-August years (33 pairs), and the clear-day fit by 0.326. The pooled fit holds one mix per Primary across its years, so the year-to-year test does not apply to the pooled fit. The pooled fit's 95% intervals (200 resamples of 7-day blocks of clear days) are on average 0.49 wide, on a share that runs from 0 to 1.

Figure 5: shares of the free fit per Primary and season-year

Primary Capacity (MW) East South West
Kirton (experiment 40 flagged a daylight load there) 1.58 0.00 (0.00 to 0.10) 0.95 (0.68 to 1.00) 0.05 (0.00 to 0.29)
Trusthorpe 7.58 0.33 (0.01 to 0.49) 0.08 (0.00 to 0.40) 0.58 (0.41 to 0.65)
Spilsby 2.57 0.27 (0.07 to 0.44) 0.24 (0.00 to 0.66) 0.49 (0.21 to 0.65)
Horncastle 3.03 0.31 (0.00 to 0.49) 0.19 (0.00 to 0.66) 0.50 (0.30 to 0.59)
Mount Bridge Boston 3.65 0.06 (0.00 to 0.30) 0.51 (0.19 to 0.75) 0.43 (0.23 to 0.57)
Wrangle T1 (little power) 3.71 0.27 (0.00 to 0.64) 0.23 (0.00 to 1.00) 0.50 (0.00 to 0.92)
Donington 3.27 0.30 (0.00 to 0.48) 0.23 (0.00 to 0.58) 0.46 (0.32 to 0.59)
Wrangle T2 2.69 0.49 (0.18 to 0.89) 0.29 (0.00 to 0.71) 0.22 (0.00 to 0.53)

The capacity column is the mean of the years' south-only capacities times the sum of the shares. It differs from experiment 40's capacities (for example 7.58 MW against 2.48 MW at Trusthorpe). The orientation fit trades capacity against shape, so these totals are not capacity estimates.

Figure 6: pooled shares with 95% intervals

The fitted mix predicts held-out blocks better than all-south panels at all 8 Primaries. Each fit uses alternate 28-day blocks of a season-year, and the other blocks are scored, in both directions. The south-only comparator has the same total capacity as the mix, so the two differ only in shape. C3, the relative change in held-out root mean square error of daylight power, is -1.3% (98.75% interval -2.4% to -0.5%, 80 held-out year-folds). The threshold for a gain is an upper limit below -0.5%, and the upper limit is -0.54%, so C3 is a gain by a narrow margin. The change ranges from -0.1% at Kirton to -3.8% at Trusthorpe. C4, the same comparison for the DC:AC ratio, was not computed, because the DC:AC fit failed its known answers.

Figure 7: held-out change in error by Primary

The blend improves the fit although its shares are not identified. The three shapes let the fit place solar output earlier or later in the day. Evening demand that resembles west-facing output would give the same gain, and this experiment cannot separate the two.

Five of the 8 Primaries have a pooled west share of 0.46 to 0.58, against 0.2 in the fleet mix. The interval of Wrangle T1 runs from 0.00 to 0.92, so 4 Primaries support a lean: the intervals of Spilsby (0.21 to 0.65), Horncastle (0.30 to 0.59), Donington (0.32 to 0.59), and Trusthorpe (0.41 to 0.65) all exclude 0.2.

Changes from the plan

  • The held-out cell minimum is 5 rows, not 20. With alternate 28-day blocks, no cell reached 20 fitted rows, so every held-out row was dropped in the first run. The change was made before any held-out result existed.
  • The null arm became a bootstrap. The plan injected nothing and reported the fitted shares, but with no injection the fitted capacities do not change, so the increment is exactly zero by construction. The page reports the pooled shares' 95% intervals from resampled blocks.
  • The noisy known-answer test was added after the code review and is reported beside the pre-registered test. The verdict follows the pre-registered rule.
  • The held-out comparison rescales the shares to a common total. The first version, before the code review, compared the unnormalised pooled capacities with the south-only capacity, which mixed shape and total capacity, and gave +0.8% (-0.9% to +2.8%). The corrected comparison gives the figures above.
  • The pooled arm with ridge 0 won the tuning, so the ridge prior toward the fleet mix never entered the chosen arm.
  • The knee gate uses each farm's median across its farm-years, and not each farm-year.
  • The 5 MW injection was dropped, as the plan review advised, and the 10 MW injection decides.
  • DC:AC has no fitted parameter beyond its grid, so all 6 farms are scored, and no tuning split applies. The 8 Primaries' own series were searched without injection as a reference only (41 Primary-years, quartiles 1.00, 1.00, and 1.30, range 1.00 to 1.60). The plan stops real-series fits for DC:AC, and this reference is not a claim about the Primaries.

Caveats

  • The known answers use one physics. Passing the known answers is necessary and not sufficient, as the 15° robustness arm shows.
  • Farms A to C and D to F share the same 8 Primaries, so the tuning and scoring split gives little independence. The Primary-cluster interval is reported beside the farm-cluster interval.
  • Only 6 farms score DC:AC, so the count of farms where the fit beats the guess is a coarse test.
  • The plan had one Sonnet review and no Opus review.
  • The pooled fit takes each year's total from a south-only fit, floored at 0.1 MW. East-heavy or west-heavy fleets then have shares that sum to more than 1, which is why the pooled capacity differs from experiment 40's capacity. The held-out comparison rescales the shares to a common total.
  • The 6-farm inner join drops Primary rows where any farm location's CAMS reliability is under 0.9, a small loss correlated in time.

What the next experiment should answer

The next experiment should ask whether the fitted solar shape lowers the error of the forecasts of experiment 64 (PVDIS-5), and not only the error of the fit. The held-out gain of 1.3% is for the daylight power of a fit with the weather inputs known, and a forecast has only forecast weather. The test is whether the per-Primary shape, used as the solar term of experiment 64's arm am, lowers that arm's score by more than the 0.5% threshold. The shares that make up the shape should stay fixed across all training years, or drift only under a strong year-to-year penalty. Refitting the shares freely each year would carry into the forecast the median change of 0.24 between consecutive years that the free fit shows, which is noise.

A second test should compare the west capacity fitted on daylight rows with the response of demand after dark. If the two match, the west share is probably evening demand and not panels. The test fits the same three shapes to rows after sunset, where no solar exists.

Method

Size: medium

  • What gets stored: only private work tables under data/ml-experiments/; no Delta table.
  • Serving path: untouched.
  • Degradation rule: untouched.
  • More than one defensible design: yes, so the plan fixes three orientation fits and one clipping search before any result.
  • Callers: the machinery is experiment 39's and 40's code, copied into this folder; no caller outside ml-experiments/.

The process was the full one, with Sonnet throughout: a plan, one plan review, an implementation, a code review, and a write-up with a prose review.

Earlier advice followed

  • From experiment 40: do not quote a capacity without a bound, and leave Wrangle T1 out of any claim that a Primary is free of a load. Every real-series table here flags Kirton and Wrangle T1.
  • From experiment 45: the capacity is held constant within each season-year, not weekly.
  • Departure: none.

Data and fits

Inputs are experiment 39's frame, read and never rebuilt: half-hourly power of the 8 directional Primaries and 6 solar farms, CAMS irradiance, and ERA5 temperature, on daylight half-hours (zenith under 75°). The fit window is April to September of each season-year. The demand term is the calendar-cell term of experiment 40's arm M2h (fixed effect per month, half-hour, and day type, heating degree-days, and cloud terms in three hour bands). The solar shapes come from studies.pv_separation.solar_basis at 25° tilt, which gives the AC output of 1 MW of east-, south-, and west-facing panels, clipped at min(r × irradiance / 1000, 1).

Orientation arms. Each fits non-negative east, south, and west capacities to a Primary's season-year.

  • O1, free: three free capacities.
  • O2, free on clear days: O1 on days whose mean cloud response is below 0.15. The cloud response is 1 - min(ghi_u / ghi_u_clear, 1) at the Primary's CAMS point, averaged over the day's daylight half-hours (experiment 39's frame columns). A Primary-year needs at least 20 clear days or it is dropped from O2 and O3 and the count is reported.
  • O3, pooled with a prior: one mix per Primary shared by all its season-years, clear days only, with a ridge penalty pulling the shares towards the fleet mix. The penalty is chosen on tuning units from the grid 0, 0.1, 1, 10 (relative to the mean squared column norm).
  • References: G guesses the fleet mix; S assumes all south.

DC:AC arm. For each ratio r on the grid 1.00, 1.05, ..., 1.60, fit one capacity to the clear-day rows with the shape min(r × irradiance / 1000, 1) (south, 25° tilt) and keep the r with the lowest residual sum of squares. A ratio of 1.00 never clips in GB. The interval is the 2.5th to 97.5th percentile of the best r over 200 resamples of 7-day blocks.

Known answers, run before any real fit

  • Orientation: inject 3 MW of synthetic output, 3 × (wE uE + wS uS + wW uW) with the shapes built from CAMS at each solar farm's location, so the injected sky differs from the sky the fit uses at the Primary. A robustness arm, reported and not decisive, injects shapes at 15° and 40° tilt while the fit stays at 25°, and passing the known answers is necessary but not sufficient. The five true mixes (wE, wS, wW) are (0, 1, 0), (0.2, 0.6, 0.2), (0.5, 0.4, 0.1), (0.1, 0.4, 0.5), and (0.5, 0, 0.5). Units are Primary × season-year × farm location × mix. The estimated shares come from the increment of the fitted capacities, with negative increments set to zero. A total increment under 0.3 MW counts as an error of 0.5. Each arm reports the share of units that hit either rule.
  • DC:AC: the DC:AC ratios of the six farms are experiment 29's PyTorch fits: 1.15, 1.17, 1.22, 1.42, 1.12, and 1.26. Run the search on each farm's output alone against its own location's shape, and on each farm's output scaled to 10 MW and added to a Primary's real series. The farms are tuned and scored in the same split as orientation (A to C, D to F).
  • Noisy known answer (added after the code review): rebuild each series with no solar of its own and day-shuffled residuals, inject the known output, and score the fitted capacities directly, because the increment test above is blind to noise.
  • Self-tests that stop the run: a made-up all-south mix reproduces the south-only fit; noise-free injection into zero demand returns the true mix to 1e-6; noise-free clipped output returns the true ratio; linearity of the increment.

Real series

The real-series fits use the same designs. The free and clear-day fits are per season-year. The pooled fit has a 200-draw block bootstrap. Contrast C3 fits on alternate 28-day blocks, scores the others, and reverses, with the capacities fixed from the training blocks and the calendar cells and nuisance terms refitted on them.